Page view 49
NetworkAIR ACPA400042
Specifications
Electrical
Input voltage 115 V; 60 Hz; 1 Ph
Rated current 14.4 A
Physical
Physical dimensions
W × D × H
584 × 724 × 980 mm
(23 × 28.5 × 38.6 in)
Net weight (equipment
only)
79 kg (175 lb)
Shipping weight 88 kg (195 lb)
Component Type
Compressor type Rotary
Refrigerant HCFC R22 (2.0 lb)
Air filter (
ACPA4000RF)
W × D × H
406.4 × 50.8 × 406.4 mm (nominal)
(16 × 2 × 16 in)
Cooling Capacity
Total BTU/hr (kW)
Sensible BTU/hr (kW)
35°C (95°F) at 61% RH
13,000 (3.81)
7,000 (2.05)
22°C (72°F) at 50% RH
10,000 (2.96)
8,500 (2.50)
Note: Entering air to the condenser at a temperature over 35° C (95° F) will reduce cooling
capacity performance.
Environmental
Airflow High: 660 CFM
Low: 450 CFM
Sound level 62 dB
Dehumidifier
value
0.98 L/h maximum (0.26 gal/h)
Condensate Management
Hose length 15.24 m (50 ft) with 4.88 m (16 ft)
vertical lift maximum
Hose diameter 6.35 mm (1/4 in) OD