MX28B-1200 PRODUCT MANUAL Revision B
44 MX28B-1200/2400
(Table 6-1. Parameter Locations, Descriptions, and Default Values)
PARAMETER DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Standby Alarm {1}
[MODULES/RECT/SET-ALM]
This alarm indicates that the control unit is holding a rectifier
in the standby mode.
Rect Stdby Almm+
nofN
Fan Fail Alarm {1}
[MODULES/RECT/SET-ALM]
This alarm indicates that a rectifier fan has failed.
Rect FF Alm m+
nofN
RFA Alarm {1}
[MODULES/RECT/SET-ALM]
This alarm indicates that a rectifier output has failed.
Rect RFA Alm m+
nofN
CIRCUIT BREAKER SETUP
Breaker 1 Alias {1}
[MODULES/CIRBKR/ALIAS]
An alternate name (alias) that can be assigned to a circuit
breaker if desired.
Cir Bkr 1 m+
-48V
Breaker 72 Alias {1}
[MODULES/CIRBKR/ALIAS]
An alternate name (alias) that can be assigned to a circuit
breaker if desired.
Cir Bkr 72 m+
-48V
Circuit Breaker Alarms
Breaker 1 Tripped {1}
[MODULES/CIRBKR/SET-ALM]
An alarm that indicates Circuit Breaker 1 is tripped.
Cir Bkr 1 Alm m+
Major
Breaker 72 Tripped {1}
[MODULES/CIRBKR/SET-ALM]
An alarm that indicates Circuit Breaker 24 is tripped.
Cir Bkr 72 Almm+
Major
FUSE SETUP
Fuse 1 Alias {1}
[MODULES/FUSE/ALIAS]
An alternate name (alias) that can be assigned to a Fuse 1 if
desired.
FUSE 1 +
-48V
Fuse 16 Alias {1}
[MODULES/FUSE/ALIAS]
An alternate name (alias) that can be assigned to a Fuse 16 if
desired.
FUSE 16 +
-48V