MX28B-1200 PRODUCT MANUAL Revision B
46 MX28B-1200/2400
(Table 6-1. Parameter Locations, Descriptions, and Default Values)
PARAMETER DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Output Relay Major Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay if
desired.
Relay Major m+
Major
Output Relay 1 Delay {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Delay between sensing of the alarm condition and activation
of the alarm relay. An alarm condition must exist for longer
than the delay to be activated.
Out-Rly 1 Dly m+
0 sec
Output Relay 6 Delay {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Delay between sensing of the alarm condition and activation
of the alarm relay. An alarm condition must exist for longer
than the delay to be activated.
Out-Rly 6 Dly m+
0 sec
Output Relay Alarms
Output Relay 1 {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Output Relay 1 alarm can be “mapped” to activate other
output relays (“Ignore” activates no additional relays).
Out-Rly 1 Alm m+
Ignore
Output Relay 6 {1}
[SYSTEM/OUT-RLY/RLY-MAP]
Output Relay 6 alarm can be “mapped” to activate other
output relays (“Ignore” activates no additional relays).
Out-Rly 6 Alm m+
Ignore
LVD SETUP
LVD1 Trip {1}
[MODULES/LVD/PARAM]
LVD1 trip (disconnect) threshold voltage.
LVD1 Trip m+
-42.00 V
LVD1 Restore {1}
[MODULES/LVD/PARAM]
LVD1 restore (reconnect) threshold voltage.
LVD1 Reset m+
-48.00 V
LVD2 Trip {1}
[MODULES/LVD/PARAM]
LVD2 trip (disconnect) threshold voltage.
LVD2 Trip m+
-42.00 V
LVD2 Restore {1}
[MODULES/LVD/PARAM]
LVD2 restore (reconnect) threshold voltage.
LVD2 Reset m+
-48.00 V
LVD Alarm
LVD1 Option {1}
[MODULES/LVD/SET-ALM]
Set to “Enable” if the unit has an LVD1.
LVD1 Option m+
Enable
LVD1 Alarm {1}
[MODULES/LVD/SET-ALM]
Sets the priority or “mapping” of an LVD1 Alarm.
LVD1 Open Alm m+
Minor
LVD2 Option {1}
[MODULES/LVD/SET-ALM]
Set to “Enable” if the unit has an LVD2.
LVD2 Option m+
Enable
LVD2 Alarm {1}
[MODULES/LVD/SET-ALM]
Sets the priority or “mapping” of an LVD2 Alarm.
LVD2 Open Alm m+
Minor