3.0 Details of Service
3.1 START-UP SERVICES
The specific features and deliverables of this service are listed below. For each item listed below,
APC-MGE will perform the work described and create a printed document summarizing the results.
System Environment
Activities Description
Environmental Requirements
APC-MGE will check the
Smart-UPS
®
RT 15/20 kVA to ensure
there are no signs of damage, the environment is suitable for
operation and that there will be sufficient clearance around the s
y
stem
for service.
APC-MGE will verify the Smart-UPS
®
RT 15/20 kVA System is
positioned properly and all Netshelter and InfraStruXure
Management accessories are installed (if applicable).
APC-MGE will check that the Input Circuit Breaker and transformer
(if applicable) in the
Smart-UPS
®
RT 15/20 kVA System is sized
properly, the power wiring to the system Input Circuit Breaker is
correct and the Grounding Electrode Conductor (GEC) is installed
properly.
APC-MGE will check that the incoming voltages match the
nameplate phase and voltage listing the system is properly
grounded.
APC-MGE will verify that all power connections are properly torqued
and meet applicable national and local codes.
APC-MGE will check that all racks are level and aligned properly.
Installation Check
APC-MGE will confirm all enclosures are properly labeled.
Battery Visual and Safety
Inspection
APC-MGE will ensure the mechanical integrity is intact of the battery
rack or cabinet, measure and record the ambient temperature, and
record the serial numbers of the batteries where applicable.