Menu Item Definitions
Outlets
Control
Continued on next page
Item Definition
Immediate On
Immediately turns an outlet on. This command is available any
time after the unit’s Power On Time Delay has expired and the
outlet is off. (Available in both Annunciator and Graceful
Shutdown modes.)
Sequenced On
Turns on every outlet according to its Power On Delay time.
(This is only available for Master Control of Outlets in Graceful
Shutdown mode.)
Delayed On
Turnsanoutletonaftertheoutlet’s Turn On Delay expires.
The “Delayed On Sequence” on page 21 illustrates this
command. This command is available any time after the unit’s
Power On Time Delay has expired and the outlet is off. (Only
available in Graceful Shutdown mode.)
Immediate Off
Immediately turns an outlet off. (Available in both Annuciator
and Graceful Shutdown modes.)
Graceful Reboot
Gracefully shuts down and restarts an outlet. If the server is
running shutdown software, such as PowerChute Plus, and is
connected to MasterSwitch plus with the appropriate signaling
cable, this operation will ensure that your server’s operating
system is shutdown before the outlet is turned off. Otherwise,
it will turn off the outlet after the Power Off Time Delay expires.
The outlet will be restarted after the Reboot Duration expires.
The “Graceful Reboot Sequence” on page 23 illustrates the
this command. (Only available in Graceful Shutdown mode.)
Note: If this command is applied to all outlets, then the
Reboot Duration delay for an outlet will not begin until
all the outlets have shut down.