Problem Possible Cause Solution
A server connected
to a Basic port
does not detect On
Battery or Low
Battery signal.
Wrong cable is being
used.
Verify that you are using the correct
cable. Refer to Choosing additional
cables: Table 1,in the Installation
and Quick Start Manual.
Server shutdown
software is not
configured for simple
signaling.
Configure PowerChute Plus for
simple signaling. For instructions,
see the documentation supplied
with PowerChute Plus.
One or more
servers shuts down
when the
UPS
is on
battery, but does
not reboot when
power returns
PowerChute Plus is
configured to start
shutdown on an
AC
Fail event and the
shutdown time for
operating system is
set too short.
If the MasterSwitch plus Low Battery
Warning Control is set to
Programmed Delay, make the delay
shorter than the
AC
Fail shutdown
delay in PowerChute Plus
FlexEvents.
MasterSwitch plus
Low Battery Warning
Control
is set to Programmed
Delay
If the server is capable of
UPS
shutdown, consider setting the Will
Device Confirm property to Yes.
To
UPS
Status
LED
is flashing green
and red.
Communication cable
is not fastened
securely or the wrong
cable is being used.
Verify that all cables are securely
fastened and that the cable has
APC
part number
940-1000
.
UPS
is connected to
the wrong port.
Verify that the
UPS
is connected to
the To
UPS
port on MasterSwitch
plus.