Symmetra MW II with Internal Bypass Static Switch - Operation - 990-1756C-00112
3. Press Initiate Transfer.
4. Verify that the status in the upper right corner has
changed to Static Bypass.
How to transfer from static bypass to normal operation
1. Press the Operation button on the UPS Summary
screen.
2. Press the Static Bypass -> Online button. Press inside
the password field and type in the user password using
the keyboard on the screen. Complete with
ENTER.
3. Press Initiate Transfer.
4. Verify that the status in the upper right corner has
changed to Normal.