APC Network Management Card AP9619 User Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 34
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
UPS Overview – Navigation
8 Smart-UPS® VT ISX 20-30 kVA, 208/220/480V Operation 990-2819
Switch load OFF (disconnect the UPS output to the load equipment):
From the Main Menu, select Control and press ENTER
Use UP/DOWN key to navigate to Turn Load Off, and press ENTER
Select YES, Turn Load Off
Switch load ON:
From the Main Menu, select Control and press ENTER
Use UP/DOWN key to navigate to Turn Load On, and press ENTER
Select YES, Turn Load On
Switch into bypass:
From the Main Menu, select Control and press ENTER
Use UP/DOWN key to navigate to UPS into Bypass and press ENTER
Use UP/DOWN key to navigate to YES, UPS into bypass, and press ENTER
Switch out of bypass:
From the Main Menu, select Control and press ENTER
Select UPS out of Bypass and press ENTER
Use UP/DOWN key to navigate to YES, UPS out of Byp, and press ENTER
Status views
Select Status on the Main Menu to view the status on the following parameters
Voltage on all phases.
Utility voltage (V), bypass voltage (V), and output voltage (V) for each phase.
Current on all phases.
Utility current (A), bypass current (A), and output current (A) for each phase.
kVA and kW.
Apparent power (kVA) and real power (kW) generated by the UPS to the load.
Control
Status
Setup
Logging
Display
Diags
Help
Main Menu
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 33 34

Comments to this Manuals

No comments