41Metered-by-Outlet With Switching Rack PDU User Guide
olNearOver
Access: Administrator, Device User
Description: Set or view the outlet near-overload threshold in kilowatts. To specify outlets, choose
from the following options.
Example 1: To set the near-overload threshold for all outlets to 10 kW, type:
apc> olNearOver all 10
E000: Success
Example 2: To view the near-overload threshold for outlets 1 through 5, type:
apc> olNearOver 1-5
E000: Success
1: 10 kW
2: 10 kW
3: 10 kW
4: 10 kW
5: 10 kW
Example 3: To set the near-overload threshold for all outlets on guest Rack PDU 3 to 10 kW, type:
apc> olNearOver 3:all 10
E000: Success
olOff
Access: Administrator, Device User, and Outlet User, but only for outlets to which the user is assigned.
Description: Turn off an outlet or group of outlets without any delay.
Example 1: To turn off outlets 3 and 5 through 7, type:
apc> olOff 3,5-7
E000: Success
Example 2: To turn off outlets 1 through 3 on guest Rack PDU 2, type:
apc> olOff 2:1-3
E000: Success
Argument Definition
all All device outlets.
<outlet#> A single number or a range of numbers separated with a dash, or a comma-
separated list of single outlet numbers and number ranges.
Argument Definition
all All device outlets.
<outlet name> The name configured for a specific outlet. (See “olName” on page 40.)
<outlet#> A single number or a range of numbers separated with a dash, or a comma-
separated list of single outlet numbers and number ranges.