MasterSwitch Power Receptacles continued
Warnings Exceeding the voltage or amperage limits for the individual
Power Receptacles could cause fire damage or shock.
Do not exceed the load capacity of the
UPS or branch circuit by
connecting more than one fully loaded Power Receptacle. To
calculate the expected load, consult the nameplate ratings of all
connected equipment.
You must maintain reliable grounding of all equipment. Pay
particular attention to supply connections other than direct
connections to the branch circuit.
Do not exceed the operating temperature or humidity limits
shown in Additional specifications on page 5. Note that the
ambient temperature in a rack environment may be greater than
the ambient room temperature.
When installing the Power Receptacles in a rack:
Do not mount the receptacles in a location that impedes
the flow of air in the rack.
Do not mount the receptacles in a way that loads the
rack unevenly, causing the rack to become unstable.
Disconnect the front panel power cord and the relay control
input cord before moving the Power Receptacle. Both cords
carry hazardous voltages.
Mounting
power
receptacles in a
rack
To mount Power Receptacles in a NetShelter enclosure or other
standard (
EIA 310-D) 19" rack, use the hardware provided with
the Power Receptacle Tray and perform the following steps in
the order given.
1. Plan the mounting location for the tray and each unit
within the tray. The figure on page 4 shows the tray
mounted at the rear of a NetShelter, at the same height
as the MasterSwitch, which has been mounted on the
front. Consider your need for proximity to the UPS and
to the attached load(s).
Note: You must install Power Receptacles near the attached
load(s), so that the outlet is easily accessible.