Maintenance: Parts Replacement
990-3054B-001 Modular Power Distribution Unit – Operation 17
How to install a Power Distribution Module
Electrical Hazard: To prevent arcing when removing an APC Power Distribution Module
(PDM) from the Modular Power Distribution Unit (PDU), set all PDMs to
OFF. Do not
remove the modules when they are under load.
Caution: PDMs must be replaced by trained personnel only (see the section "Safety").
Note: The PDM can be safely installed into a powered rack.
Note: For PDMs with RCDs installed, the occurrence of an earth fault will automatically open
the adjacent circuit-breaker. (See the below drawing under "PDMs with RCDs").
Note: PDMs with RCDs are equipped with a test button. Periodic testing of the RCD may be
required. Check your local codes for your region. (See the section "Note: Do not throw away
the filler plate. Keep it for potential later use.").
ON
position
ON
position
PDM – Single and Three
phase
PDM with RCD (Residual Current
Devices) - Three phase
PDM with RCD – Single phase
ON
position
PDMs with RCDs
An earth fault will open the
adjacent circuit breaker to the
OFF
position. The fault is indicated by a
red strip on the RCD toggle.
The circuit breaker has been closed
manually by pushing the toggle to the
ON position.
Test
button
Test
button