415V Site Considerations
Any 480V output UPS with a 5 wire output can feed the Modular PDU.
Symmetra PX 250/500 has an integrated 480V sub-feed panel that is optimized for this type of
application.
Neutral must be provided from the building service entrance, through the UPS, due to the
autotransformer technology implemented.
Autotransformer technology possesses only one set of windings, and does not develop or derive a
neutral.
UL requires all UPS sub-feed wiring to be contained in the same conduit.
Each PDU feed will have 5 Wires (3 phases, Neutral, and Ground).
C13/C19 input cords are acceptable for rack loads
This voltage product will not support L5-20/L6-30 corded equipment.
42-inch rear clearance is required for the PDU
This product is not compatible with the current Hot-Aisle Containment System (HACS)
Custom 48” roof tile adapters for HACS are available thru CEG
A solution for 36” hot aisle applications is under development