APC by Schneider Electric – Mark Tarantelli – 4 November 2008
415V Site Considerations
● Any 480V output UPS with a 5 wire output can feed the Modular PDU.
● Symmetra PX 250/500 has an integrated 480V sub-feed panel that is optimized for this type of
application.
● Neutral must be provided from the building service entrance, through the UPS, due to the
autotransformer technology implemented.
● Autotransformer technology possesses only one set of windings, and does not develop or derive a
neutral.
● UL requires all UPS sub-feed wiring to be contained in the same conduit.
● Each PDU feed will have 5 Wires (3 phases, Neutral, and Ground).
● C13/C19 input cords are acceptable for rack loads
● This voltage product will not support L5-20/L6-30 corded equipment.
● 42-inch rear clearance is required for the PDU
● This product is not compatible with the current Hot-Aisle Containment System (HACS)
● Custom 48” roof tile adapters for HACS are available thru CEG
● A solution for 36” hot aisle applications is under development