CHAPTER 3: MENU COMMANDS
14
Setup Menu (continued)
Menu Item Function Options
Alarms Sets the alarm thresholds. None
Redundancy An audible alarm sounds if the redundancy falls
below this level.
0(default), 1, or 2
Load An audible alarm sounds when the load exceeds
this limit. (Upper value is limited by the maximum
power of the UPS.)
Never(default), 1, 2, 3, 4, 5,
6, 7, 8, 9, 10, or 12 kVA
Runtime An audible alarm sounds if the available runtime
falls below this level (Hours:min).
0:0(default),5m, 10m, 15m,
30m, 45m,1h, 2h, 3h, 4h,
5h, 6h, 7h, or 8h
Bypass In the unlikely event that both the UPS fails and
the input voltage or line frequency is outside of
normal range, this option lets you choose to go
into Bypass mode or drop the load.
Go to Bypass or
Drop Load
Copy Select the configuration that you wish to move
UPS data into or out of, and t hen select the
direction that you wish to move the data.
Note: Copying data between different voltage
versions may not yield optimum results; in
particular, the output voltage selection should be
reviewed by the user. Copying between different
product lines may leave some parameters in the
target UPS set to factory defaults, especially
when copying from a product with less capability
to one with more capability.
Options include:
Configuration Number,
from UPS to Display, and
from Display to UPS.
Copy command definition
found in Powerview
manual, 990-0142, page
11.
Other Remaining user-defined settings.
Self Test The UPS can automatically test itself at this
user-specified interval.
At Power On, 7 days,
14 days(default) , or
Disabled
UPS ID Assigns an eight-character text string to a
system.
Output Sets output voltage. Selection depends upon
system configuration.
US/JAPAN:
200V, 208V, 240V
INTERNATIONAL:
220V, 230V, 240V
Vout Reporting Reports the most significant output voltage. Auto