Rack-mount Product Specifications
Symmetra Rack-mount 208 VAC (Output) 120; 208 VAC (Output) 220; 230; 240 VAC (Output)
System Part No. SYP8K12RMT SYP12K12RMT SYP8K12RMT-P1 SYP12K12RMT-P1 SYP12K12RMT-P2 SYP8K12RMI SYP12K12RMI
Output
Capacity 8kVA/5.6kW 12kVA/8.4kW 8kVA/5.6kW 12kVA/8.4kW 12kVA/8.4kW 8kVA/5.6kW 12kVA/8.4kW
Voltage Input 208 or 240 208 220,230,240V
Family Symmetra RM
Output Voltage 208 (240 configurable) 220,230,240V
Max Configurable Power with
additional Power Modules 12kVA/8.4kW (N+1), 16kVA/11.2 kW (N only)
Output Connections (6) NEMA L6-20R, (6) NEMA L6-20R, (2) NEMA L6-30R, (6) NEMA L6-20R, (24) IEC 320 C13;
(3) NEMA L6-30R, Hardwiring 12 NEMA 5-20R*, Hardwiring (1) NEMA L6-30R, 24 (6) IEC 320 C19
NEMA 5-20R*,
Hardwiring
Efficiency at full load 91% 87% 91%
By pass Internal Bypass (Automatic & Manual)
Output voltage Distortion typically <5% at full load (linear or non-linear)
Output frequency (synched to mains) 57-63Hz 47-53%
Output frequency (not synched) 60Hz 50 Hz
Crest Factor up to 5:1
Input
Nominal input Voltage 208 or 240 208 220,230,240V
Input Frequency 50/60 Hz +/- 5Hz. (auto sensing)
Input Connection Hardwire (3-wire)
Input Voltage range 155-276V
Input Power Factor at full load 0.98
Batteries
Battery Type Maintenance - free, sealed lead acid battery with suspended electrolyte, leakproof
Typical recharge time 3 hrs.
Replacement Battery Cartridge (2) SYBT3 (3) SYBT3 (2) SYBT3 (3) SYBT3 (3) SYBT3 (2) SYBT3 (3) SYBT3
Communications and Management
Interface port DB-9; RS-232; Smart-Slot Card (2)
Management Software included PowerChute Network Shutdown, Web/SNMP Management Card ships standard
Control panel Multi-function LCD status & control console in Multiple Languages
Audible Alarm Alarm when on-battery; distinctive low battery alarm; configurable delays
Emergency Power Off (EPO) Yes
Physical
Dimensions HxWxD** (in/cm) 15U/26.25x19x27.2” 17U/29.75x19x27.2” 19U/ 33.25x19x27.2” 15U/26.25x19x27.2”
66.7x48.3x69.1cm 75.75x48.3x69.1cm 84.46x48.3x69.1cm 66.7x48.3x69.1cm
Weight net (lbs) 358 452 453 547 642 358 452
Weight shipping 398 492 503 597 692 398 492
Environmental
Operating Temperature 0-40 C/32 - 104 F
Operating Relative humidity 0-95%
Operating Elevation 0-10000 feet/0-3000m
Storage Temperature -15 to 45C/5 to 113F
Storage Relative Humidity 0-95%
Storage Elevation 0-50,000 ft/0-15,000m
Audible noise at 3 feet (1 m) 62dBA
On-line thermal dissipation (BTU/hr) 1889 2834 2855 4282 4282 1889 2834
Conformance
Approvals CSA; FCC A; UL 1778 C-tick; EN 50091-2;VDE
Warranty/Service Options
Warranty 2 years, repair or replace(1 year for battery modules in India)
"T" level for Service Option pricing T7 T7 T7 T7 T7 T9 T9