NetShelter SV User Manual8
Joining Cabinets
Cabinets can be joined with or without side panels installed to provide for alignment and some stability.
The cabinets are shipped with pre-installed joining brackets for 600 mm centers. To join on 24 in.
centers, the cabinet is provided with 24 in. joining brackets in the hardware bag.
1. Remove the front and rear doors.
2. The cabinet is preinstalled with 600 mm centers. To join with 24 in. centers, replace the
preinstalled joining brackets with 24 in. joining brackets (provided in the hardware bag).
3. Align the cabinets and join them using one M5 x 12 flat-head screw (provided in the hardware
bag) per bracket—two brackets for the front and two brackets for the rear.
4. Reinstall the doors.
WARNING
TIP HAZARD
Joining cabinets provides limited stability. Ensure the cabinet is secured to the floor before
installing equipment.
Failure to follow these instructions can result in serious injury or equipment
damage.
ns2005a
600 mm
x 4