Advanced View: Defining Thresholds
154 Using Your Appliance
your appliance. To include images from one or more connected Camera Pod 120s, check the
check boxes that correspond to the desired pods.
–Specify a User-specified URL and User-specified Description. You can use these fields to
include additional user-specific information with any alert notifications that are generated using
this threshold.
8. Click OK to save this threshold.
Defining State Thresholds
Detailed instructions on how to define each of the available state threshold types follow.
Alert State Threshold
An alert state threshold is defined by specifying the state which, if reported by the sensor, will cause an
alert condition to be reported. If the state reported by the sensor is the specified state for any length of
time an alert condition is reported. To define an alert state threshold:
1. Start the Camera Pods, Sensor Pods, or Device Crawlers task by double-clicking on the appropriate
icon.
2. Click Sensors... to open the Sensor Configuration window.
3. Select from the Sensors selection list the sensor for which you will define a threshold. A list of
thresholds that have been previously defined for the selected sensor, if any, appears in the
Thresholds selection list.
4. Click Add... to open the Select Threshold window. Select Alert State Threshold and then click OK
to close the Select Threshold window.
5. Type in the Threshold Name field a name for this threshold.
6. Specify Basic threshold settings. From the Basic tab in the Thresholds pane:
a. Select from the Alert State drop box the state that, if reported by the sensor, will result in an alert
condition.
b. Check the Enabled check box to enable the threshold. If this check box is not checked, the alert
threshold will be saved but will not be active.
c. Add to the Threshold-Specific Addresses list the e-mail addresses of any personnel to whom e-
mail alert notifications should be sent if this threshold triggers an alert condition. Click Add...,
type in the e-mail address to which the alert notification will be sent, and then click OK.
If you’ve installed an SMS-capable modem you can deliver alert notification to SMS-enabled
devices by entering threshold-specific addresses for them in the following format:
sms:sms_device_address
where sms_device_address is the telephone number or e-mail address associated with the SMS-
enabled device (for example, “sms:5123334444” or “sms:[email protected]”).
7. If desired, specify Advanced Threshold settings. All Advanced threshold settings are optional. From
Note
These threshold-specific notifications are sent only if your appliance has one or
more Alert Actions defined that use the Send E-Mail Message alert notification
method and that have the Include Addresses from Thresholds check box
checked. For more information, see “Alert Actions” on page 59 and “Advanced
View: Creating Alert Actions” on page 161.