CHAPTER 5: MAINTENANCE AND TROUBLESHOOTING
Storage
Storage Conditions
Store the battery pack covered and flat (rack mount orientation) in a cool, dry location, with its
battery fully charged. Disconnect any cables connected to the computer interface port to avoid
unnecessarily draining the battery.
Extended Storage
At -15 to +30 °C (+5 to +86 °F), charge the batteries every six months.
At +30 to +45 °C (+86 to +113 °F), charge the batteries every three months.
Replacing the Battery
The 2U battery pack and Smart-UPS 1400 use different replacement battery cartridges.
The battery cartridges are not interchangeable
This battery pack consists of two easy to replace hot-swappable battery trays. Battery replacement
is a safe procedure, isolated from electrical hazards. You may leave the battery pack connected to
the UPS and the protected equipment on for the following procedure. See your dealer or APC
(refer to How To Contact APC, page 4) for information on replacement battery trays.
Unit Replacement Shape
UPS SU1400RMXL3U RBC25
External battery pack SU24RMXLBP2U RBC26
Battery Replacement Procedure
Please read Chapter 1: Safety Information, page 1, before replacing a battery tray.
1. The battery trays are accessible from the front of the battery pack.
2. Be careful removing the battery tray—it is heavy.
3. This procedure requires a Phillips head screwdriver.