11InRow Air Cooled RD Installation
Refrigeration Piping Diagram
Note: Shutoff valves shown nearest to the condensers are not supplied by APC.
Note: Route piping through the top or bottom of the InRow RD.
Note: All lines are Type L ACR copper tubing.
Note: Trap the vertical discharge line every 6 m (20 ft) to ensure proper oil return.
Note: Change the size of the pipe after the P-trap. See the piping diagram created for your
site.
Note: The maximum piping run is 61 m (200 ft) equivalent length. Size the piping pursuant
to accepted refrigeration practice.
Warning: Do not install the air-cooled condenser below the InRow RD. The condenser
must be positioned above or at the same level as the InRow RD to ensure proper
function.
Pitch in direction of refrigerant flow; 4 mm per m
(1/2-in per 10 ft)
Check valve
Reduction of piping diameter for vertical piping run
(if necessary)
P-trap
Schrader valve S-trap
Shutoff valves Inverted P-trap
Head pressure control valve