InRow Air Cooled RD Installation16
Service access
A minimum 900 mm (36 in) of clear floor space in front of and behind the equipment is recommended
for service. All required periodic maintenance can be performed from the front or rear of the equipment.
Most of the cooling components in the equipment (e.g. dry filter, sight glass, solenoid, and expansion
valves) must be soldered for repair or replacement. Do not service these components while the
equipment is located inside the data center. Use the casters on the equipment to move it outside the data
center for service. A minimum of 1200 mm (48 in) of clear floor space in front of or behind the
equipment is recommended to roll out the equipment.
Note: Check local and national codes and regulations for additional service access
requirements.
Dimensions are shown in mm (in).
na2230a
Service access
when equipment is
inside the row
Free space needed
to move equipment