Apc 2000XL User Manual Page 39

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 38
Page 37
9.0 Specifications
9.4 Noise and surge suppression
Surge energy rating (one time, 10/1000 µs waveform): 480 J.
Surge current capability (one time, 8/20 µs waveform): 6500 Amp peak maximum.
Surge response time: 0 ns (instantaneous) normal mode, <5 ns common mode.
Surge voltage let-through: <0.3%, [<2%] of applied ANSI C62.41 Category A ± 6 kV test
waveform.
Noise filter: normal and common mode EMI/RFI suppression, 100 kHz to 10 MHz.
9.5 Battery and charger
Battery type: spill proof, maintenance free sealed lead-calcium.
Typical battery life: 3 to 6 years - depends on number of discharge cycles and ambient
temperature.
Typical recharge time: see tables in section 9.9.
9.6 Environment
Operating temperature: 0°C to 40°C (32°F to 104°F).
Storage temperature: -15°C to 45°C (5°F to 113°F).
Operating and storage relative humidity: 0 to 95%, non-condensing.
Operating elevation: 0 to 3,000 m (10,000 ft).
Storage elevation: 0 to 15,000 m (50,000 ft).
Electromagnetic immunity: IEC 801-2, 801-3, 801-4, 801-5; severity levels III or IV.
Audible noise; 600VA, 900VA models: < 50 dBA at 1 m (3 ft).
Audible noise, 2000VA models < 60 dBA at 1 m (3 ft).
9.7 Physical
Size; 600VA, 900VA models: Electronics and Battery pack enclosures each 9.1"H x 6.9"W
x 17.8"D (23.1 x 17.5 x 45.2 cm).
Size, 2000VA model: Electronics enclosures is 18.0"H x 6.9"W x 17.8"D (45.7 x 17.5 x 45.2
cm). The Battery pack is 9.1"H x 6.9"W x 17.8"D (23.1 x 17.5 x 45.2 cm).
Weight; 600VA, 900VA models: Electronics enclosure is 32 lbs (14.5 kg), shipping weight
is 37 lbs (16.8 kg). The Battery pack is 62 lbs (28.1 kg), shipping weight is 67 lbs (30.4 kg).
Weight, 2000VA model: Electronics enclosure is 61 lbs (27.7 kg), shipping weight is 68 lbs
(30.8 kg). The Battery pack is 64 lbs (29.0 kg), shipping weight is 69 lbs (31.3 kg).
9.8 Approvals
Safety approvals: UL per 1778, CSA per C22.2, TUV per IEC 950.
EMC verification: FCC, DOC Class A verified; EN55022 Class A verified.
Page view 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44

Comments to this Manuals

No comments