5.0 Operation
5.5 Option switches
The UPS has a set of four DIP switches on the rear panel which allow you
to configure several options (see Secs. 5.5.1–5.5.4).
0
(
o
f
f
)
(
o
n
)
1
2
3
4
Note: You can set option switches at any time, and the effect is immediate.
Note: If all of the option switches are set to the on position, the option switches are
disabled. However, the functions controlled by the option switches are still
available using UPS monitoring software (see Sec. 5.6.4).
5.5.1 Option Switch 1
The UPS contains utility fault detection circuitry that is extremely sensitive
to line voltage distortions including spikes, notches, sudden dips, and
swells. The UPS is factory-set to react to such line voltage distortions by
immediately transferring the load to on-battery operation, affording
maximum protection for all load types. Where power quality is poor
because of local cyclic heavy load-switching, or the use of inexpensive fuel
generators, the UPS may frequently transfer to on-battery. If the UPS is
powering loads that operate normally under such conditions, battery
capacity may be spent unnecessarily.
Setting Option Switch 1 to the on (I ) position desensitizes the UPS to rapid
low-amplitude line-voltage fluctuations, and increases the UPS’s upper
transfer voltage by 3%, for a total of 13% above the nominal input voltage.
This helps maintain maximum battery capacity for major utility failures.