Apc BC300 User Manual Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
34 Installation Guide APC BC300 Series 60kW 208/480V UPS
990-1400A
Technical Specifications
7.0 Technical Specifications
7.1 APC BC300 Series 60 kW Technical Data
Voltage 3 x 208Y/120 or
208V Delta
3 x 480Y/277
Input Rated input current 219Amps 95Amps
Voltage tolerance
- Utility
- Bypass
+10 / -15
+/- 10
+10 / -15
+/- 10
Frequency 60Hz
+/- 6% (standard)
60Hz
+/- 6% (standard)
Current distortion 0-5% THD 0-5% THD
Bypass tolerance +/- 10% +/- 10%
Output Voltage 3 x 208Y/120 3 x 480Y/277 or 3x
480 Delta
Voltage tolerance
- Static symmetrical load
- Static asymmetrical load
- Load step
+/- 1
+/- 3
+/- 5
+/- 1
+/- 3
+/- 5
Voltage distortion 0 - 3% (linear load) 0 - 3% (linear load)
Frequency
- Utility synchronized
- Free-running
60Hz
+/- 6%
+/- 0.1%
60Hz
+/- 6%
+/- 0.1%
Overload capacity
- Utility operation 60 seconds
- Utility operation 10 minutes
- Battery operation 60 seconds
- Battery operation 10 minutes
250%
150%
150%
125%
250%
150%
150%
125%
Rated output current 167 Amps 72 Amps
General Temperature
Ambient
Ideal
32 - 104
o
F
77
o
F
32 - 104
o
F
77
o
F
Humidity (non condensing) Max 95% Max 95%
Audible Noise (typical) <65 dBa <65 dBa
Efficiency
AC to AC normal operation
AC to AC economy mode
95%
97%
95%
97%
Heat dissipation - kW (BTU)
Full rated load normal operation
Full rated load economy
mode
0.8 PF load, normal operation
0.8 PF load, economy mode
3.16 (10778)
1.86 (6333)
2.53 (8622)
1.48 (5067)
3.16 (10778)
1.86 (6333)
2.53 (8622)
1.48 (5067)
Page view 33