Apc SILCON 60-80KW 208/480V UPS User Manual Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 34
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
16 User Guide APC Silcon 60-80kW 208V/480V UPS
990-4035
Stop/Start UPS and Operating the External Service Bypass
2.7 Isolating one UPS in a Parallel Configuration for Service/Maintenance
2.7.1 Isolating one UPS in a Parallel/Redundant System
In a redundant system one UPS may be isolated for service/maintenance without affecting
other parallel UPS(s).
2.7.2 Switching Back the UPS to Normal Rarallel/Redundant Operation
The UPS will automatically switch to normal operation and start load-sharing with the other
parallelled UPS(s).
Service
bypass
switch
Load
Utility
APC Silcon
UPS
APC Silcon
UPS
Action
1. Check that the remaining UPS(s) will be able to carry the load when one UPS is isolated.
2. Switch off the system to be isolated for maintenence by pushing the red OFF button.
3. Disconnect output and utility by setting output switches (Q002) to position 0 and input
switch (Q001) to position 0. Disconnect battery by opening battery breaker.
Action
1. Set the input switch (Q001) and the output switch (Q002) to position 1.
2. Charge capacitors, connect battery, and start up the UPS as described in 2.4.1. Start UPS
(from complete power down).
WARNING!
The system will discharge built-in capacitors.
ALWAYS check with a multimeter that the terminals contain no dangerous voltage before
touching the system!
Page view 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 33 34

Comments to this Manuals

No comments