Apc SMARTSLOT DP300E User Manual Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
19
Powering the Silcon Triple Chassis
continued
AP9604SR
power
considerations
The AP9604SR model receives its power from the UPS
through the supplied 24 VDC universal adapter. The total
current required by your accessories must not exceed the
850 mA limit of the power adapter.
See “Determining power requirements: Table 3” on this
page.
Determining
power
requirements:
Table 3
To determine the total amount of current required by your
accessories, add the individual current requirements for
each SmartSlot accessory to be installed in the Silcon Triple
Chassis to the current requirements of the chassis itself.
Refer to this table.
Continued on next page
Part # Accessory
Draw
(mA)
AP9207
Share-UPS UPS interface ex
p
ander 65
AP9600
Ex
p
ansion Chassis 30
AP9604
Tri
p
le Chassis 20
AP9604S[R]
Silcon Tri
p
le Chassis 90
AP9606
Web/SNMP Mana
g
ement Card 110
AP9607
Interface Ex
p
ander 45
AP9608
Call-UPSII 35
AP9612
Measure-UPSII 60
AP9825i
Isolated Extension Cable 50
AP9830
Remote Power-Off Device 35
Table 3: Determining power requirements