4
2. Safety
CAUTION!
To reduce the risk of electric shock in conditions where load equipment grounding cannot be
verified, disconnect the unit from the AC power outlet before installing a computer interface or
accessory slot signal cable. Reconnect the power cord only after all signaling connections are
made.
Connect the unit to a two-pole, three-wire grounding AC power outlet. The receptacle must be
connected to appropriate branch protection (fuse or circuit breaker). Connection to any other
type of receptacle may result in a shock hazard and violate local electrical codes.
The unit has an internal energy source (the battery). The output may be energized when the
unit is not connected to an AC power outlet.
To deenergize the outputs of the unit, first press the Off button for more than one second to
switch the unit off. Next disconnect the unit from the AC power outlet. To deenergize the unit
completely, disconnect the battery. See section 10.
This unit’s protective Earth conductor carries the leakage current from the load devices (com-
puter equipment). This unit generates approximately 1.5 mA of leakage current. To ensure a safe
limit of 3.5 mA, limit the total leakage current of the load devices to 2 mA.
Use of this equipment in life support applications where failure of this equipment can reason-
ably be expected to cause the failure of the life support equipment or to significantly effect its
safety or effectiveness is not recommended.