12 AI 3000 & XR Battery Enclosure 10-40kVA, 400V, Operation Manual – 990-2259
Basic display navigation principles
On the display, press ESC until you get to the Overview Screen, which provides you with basic
system status information.
Press UP, DOWN arrows to navigate the selector arrow and view all sub-menu screens.
Press ENTER to open the Main Menu screen. From here, you command, configure, and monitor the
system.
Control functions
From the Control Screen on the Main Menu, you can select the following functions:
1. Turn Load OFF/ON
2. Switch the UPS into Bypass/out of Bypass
Turn load OFF (disconnect the UPS output to the load equipment).
1. From the Main Menu, select Control and press ENTER
2. Use UP/DOWN key to navigate to Turn Load OFF, and press ENTER
3. Select YES, Turn Load FF
Chrg 100%
Load 000%
230Vin 000Vout 50Hz
Runtime: 0hr 0m
Overview Screen
Control
Status
Setup
Logging
Display
Diags
Help
Main Menu
WARNING!
Disconnecting the UPS output to the load, does NOT de-energize the UPS! Always
follow the Total-Power-OFF procedure if you need to de-energize the UPS in
emergency situations!
Control
Status
Setup
Logging
Display
Help
Diags
Main Menu