Network Shutdown Module V3
User guide
Network Shutdown Module V3 – User Manual Page 30/53
6.3 Create a multi-UPS configuration
For the multi-UPS configurations, you have to enter the IP address of each UPS that electrically powers the
machine hosting the Network Shutdown Module.
From the, Configuration->Communication page, please proceed as follows:
Multi-UPS configuration
Click on the Add button
Key in the first IP address
Key in the next IP addresses (Click on the Add button).
Select the Redundancy type of your installation (Parallel, STS, Sequential, Serial, Server with multiple
power supplies) according to your electrical configuration.
Note: For the Hot Standby/Sequential UPS Model refer to the specific UPS configuration
(optional) key in the Minimal number of redundant UPSs powering your system:
The default value is 0.
If you set this parameter to a higher level you will receive the Redundancy Lost alarm when you don’t
have enough redundant UPSs.
Note: We warn you against the consequences of these settings, but you also have the possibility to
trigger the shutdown action on “Redundancy Lost“ alarm in the actions settings.
Click on the Save button