APC G5USV040P005SAIO Datasheet Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
34001813EN/AF - Page 10
1. Presentation
Power-connection terminal blocks (version with built-in battery)
Power-connection terminal blocks (version with external battery)
INTN card for auxiliary interconnections of parallel UPS units
1.3 Cabinet layout (normal or false floor)
View with terminal-block protection cover
removed
(14) Terminal block for load output
(15) Terminal block for Bypass AC input
(16) Terminal block for Normal AC input
(17) Main earthing connector
(18) Secondary earthing connector (auxiliary
cabinets)
(14) Terminal block for load output
(15) Terminal block for Bypass AC input
(16) Terminal block for Normal AC input
(17) Main earthing connector
(22) Connection of external battery
(+/- poles)
(18) Secondary earthing connector (auxiliary
cabinets)
(19) DB9 connectors: exchange-current
information
(20) Screw connectors: position information
on Q5N, Q4S and Q3BP switches, from the
external bypass
(21) DB9 connectors: CAN communication
information between UPSs
The four feet of the cabinet are cylindrical, 40
mm in diameter.
The measurements opposite include cabinet
siding (panels and door).
Q1 Q4S
Q3BP
Q5N
QF1
Q1 Q4S
Q3BP
Q5N
+
-
XMS02 XMS03
XMS06 XMS07
XMS04 XMS05
19 20 21
850
33.5
33.5
712
590
70.5
33.5
70.5
33.5
33.5
33.5
170
Cable-
running
zone
Front
Page view 9