APC G5USV040P005SAIO Datasheet Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
34001813EN/AF - Page 18
2. Installation
TNC upstream, TNC,TNS or TT downstream
For separate Normal AC and Bypass AC lines from a single source
Installation with IT upstream and IT downstream
For separate Normal AC and Bypass AC lines from a single source
Installation with upstream TT and downstream TT (with upstream differential protection)
For separate Normal AC and Bypass AC lines from the same source
The upstream differential rating must be at least 3A, and conditions defined in IEC 364-4-41 must be respected.
1.the UPS internal PEN bar must be connected to the Q4S neutral upstream of Q4S
2.The UPS internal PEN bar must be connected to the Q5N neutral downstream of Q5N
3.The UPS internal PE bar must be transformed into a PEN bar (cables supplied for TNC options)
In normal operating mode:
The IMD1 controls the whole installation, including downstream from the UPS. Power to the IMD2 is switched off by the R2
relay which controls voltage presence upstream from the UPS.
If the voltage is cut or the protection is opened upstream :
The R1 relay cuts the IMD1 circuit and the R2 relay closes the IMD2 circuit thus maintaining control downstream of the UPS.
Normal AC
14
16
Bypass AC
15
N
N
Load
PEN
MLVS
PEN
PE
Normal AC
14
16
Bypass AC
15
R2
R1
CPI2
CPI
Load
PE
MLVS
PE
Normal AC
14
16
Bypass AC
15
Load
PE
MLVS
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 67 68