ProgrammableMode
ThisoperatingmodeisspecictotheMGEGalaxy5000.
Microswitch3onSA1mustbesettoON(iftwoSECIcardsareinstalledintheunit,thesecondcardmust
beidentieddifferently.Onthesecondcard,microswitch1onSA1mustbesettoON).
Inthismode,itispossibletoassignpredenedoperatingstatusconditions(seethecompletelist)tothe
variousSECIoutputrelaysandpredenedUPScommandstotheSELVinputs.
AssignmentsaremadeusingtheMGEGalaxy5000userinterface.
ListofOperatingStatusConditionsThatCanbe
AssignedtoanSECIOutput
Operatingstatus
conditions
Description
GENERALALARM
PFCfaultOR
InverterfaultOR
BypassstaticswitchfaultOR
ChargerfaultOR
ThermaloverloadonACbypassOR
ALINboardinputfuseblownOR
Q3BPandQ5NareclosedsimultaneouslyOR
ExternalQ3BPandexternalQ5NareclosedsimultaneouslyOR
EPOactivatedOR
Batterybackuptimeended,shifttowaitmodeOR
Batterytemperaturefault>45ºC,chargershutdownOR
BatterydeepdischargeOR
ChargershutdownduetobatteryroomtemperatureoutsidetolerancesOR
Abnormalpresenceofvoltageontheoutputbeforeclosingthebypassstaticswitch.
(frequencyconverter)OR
UPSindowngradedmode
-ExternalCANcommunicationfaultOR
-InternalCANcommunicationfault(GDEN,MIZNUSandCHAN)OR
-CANcablephysicallycutOR
-CANcommunicationrelayfaultOR
UPSpersonalizationfault
BATTERYFAULT
ThebatterywillsoonreachtheendofitstheoreticalservicelifeOR
Batterymustbechecked(followingafaultybatterytest)
LOADONUPS
InverterconnectedtotheloadandoperatingonnormalACinput.Batteryoperations
duetoaBPIorbatterytestaresignalledasoperationonthenormalACinput.
LOADON
AUTOMA TICBYPASS
ThestaticswitchontheACbypassisclosed.
LOADONBA TTERY
POWER
Inverterconnectedtotheloadandoperatingonbatterypower.Batteryoperationsdue
toabatterytestarenotsignalled.
LOWBATTERY
WARNING
Batteryhasreachedthelow-batterywarninglevel(voltageortime).Thetwothresholds
maybeuserset.
OVERLOAD
Oneoftheunitmodules(rectier,inverterorACbypass)isoverloaded(thermalor
instantaneous).
990-5219-001
MGEGalaxy500040-130kV A480V
23