Maintenance
LifeCycleMonitoring(LCM)
The“LifeCycleMonitoring”(LCM)functionprovidesUPSmaintenanceadvicetoguaranteeinstallation
availabilityfortheuser.
Thedisplaygivesthreemessagesenablingthefollowingtobeidentied:
StatusDisplayMessage
TheendofthecontractuallegalwarrantyEndofwarrantycheckrecommended
Regularmaintenancerequirementsandtheendof
servicelifeforconsumablecomponents
Technicalcheckrecommended
TheendofthebatteryservicelifeBatterycheckrequired
Inadditiontothesemessages,theminorfaultLED(A)lightsupandthebuzzersounds.Thesemessages
canbedeletedbypressingthefunctionkey(B).ThisalsocausesLED(A)togoout,thebuzzertostopand
theremovalofthe“GlobalAlarm”remotesignalling.
TocompletelydisableLCMindications,usethedisplaytoenterthepasswordrequiredtodisablethe
function.
26
MGEGalaxy500040-130kV A480V
990-5219-001
Comments to this Manuals