Operation on-battery is limited in duration according to available battery capacity and
load. Local users are alerted to this mode by visual and audible indicators. When on-
battery, the UPS displays available run time and emits a sequence of four beeps every
30 seconds. During an extended mains failure, the battery capacity will eventually
become too low to support the load and the UPS will shut down. The UPS alerts the
user to a low battery condition 2, 5, 7, or 10 minutes before shutdown, depending
upon the user setting. The UPS beeps once every second to warn local users of the
low battery condition. The UPS alerts remote users to on-battery operation and low
battery conditions using serial communications or simple signaling from the Computer
Interface port.
5.1.5 Bypass mode
When in bypass mode, the load is supplied power conditioned by the Isolation Unit.
However, the load is not protected from mains voltage sags, swells, or blackouts. The
UPS automatically transfers to bypass mode when a failure occurs in the Electronics
Unit, including blocked fan, battery charger fault, overtemperature, and welded main
relaysee Section 7.2 for a complete list of fault messages. The UPS also automati-
cally transfers to bypass if the EU separating screw is loosened. A manual bypass
switch on the EU is used when maintenance of the EU is required. The UPS must be
returned to on-line operation manually.
Local users are alerted to this mode by visual and audible indicators. When in bypass,
the UPS displays the reason for bypass (fan failure, EU switch actuated, etc.) and
beeps. The UPS alerts remote users to the bypass conditions via serial communica-
tions from the Computer Interface port.
5.1.6 Transfer between modes of operation
Transfer of load power to and from all modes of operation occurs synchronously with
the mains voltage phase. See the Specifications section of this manual for transfer time
ratings.