Smart-UPS C 1000/1500 VA 120 V Rack-Mount 2U 7
Feature Quick-Reference
Function Button
Timing
(seconds)
UPS
Status
Description
Power
POWER ON 0.2 Off Press the POWER ON/OFF button to turn on the UPS and operate on utility
power.
If utility input power is not available the UPS will operate on battery power.
POWER OFF 2OnPress the POWER ON/OFF button to turn off the UPS.
Display
Status Inquiry 0.2 On Verify the status or condition of the UPS. The LCD will illuminate for 60
seconds.
Continuous
Illumination/
Power-Saving
mode
2OnThe LCD will illuminate and the UPS will beep to confirm Continuous
Illumination mode is activated.
The LCD will extinguish and the Smart-UPS will beep to confirm that
Power-Saving mode is activated. While in Power-Saving mode, the LCD
will illuminate if a button is pressed, then extinguish after 60 seconds of no
activity.
Mute
Event Specific 0.2 On Disable any audible alarms caused by an event.
General Status
Enable/Disable
2OnEnable or disable the audible alarms. The Mute icon will illuminate and the
UPS will beep one time. The Mute feature will not activate unless the UPS
is operating on battery power.
Sensitivity 6OffThe Load Capacity icon will flash to indicate the UPS is in Program mode.
Use the
POWER ON/OFF button to scroll through and select Low, Medium,
and High sensitivity levels. The UPS will beep to confirm the selection.
Refer to Smart-UPS sensitivity settings on page 4 for details.
Self-Test 6OnThe Smart-UPS will run a test of the internal battery.
Note: This will happen automatically when the UPS is turned on.
Event Reset 0.2 On When the Event screen is visible, press and hold
DISPLAY, then press the
POWER button to clear the utility failure event counter.
Fault Reset 2FaultAfter a fault has been identified, press the POWER ON/OFF button to remove
the visual indication and return to standby status.