APC SMARTUPS Smart-UPS 2200 User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
5
Standard Tower models
Product feature SMT750 SMT1000 SMT1500 SMT2200 SMT3000
Output
Power capacity
500 W/750 VA 700 W/1,000 VA 1,000 W/1,440 VA 1,980 W/2,200 VA 2,700 W/3,000 VA
Nominal output voltage
120 V
Output frequency
57 – 63 Hz
Waveform type
Sine wave
Output connections (NEMA)
(6) 5-15R (8) 5-15R (8) 5-15R
(2) 5-20R
Switched outlet groups
- 1
Input
Nominal input voltage
120 V
Input voltage range for main operations
(Max adjustable range)
82 – 144 V (75 – 154 V)
Input frequency
50/60 Hz +/- 3 Hz (auto sensing)
Input connection
5-15P, 6 ft. cord 5-20P L5-30P
Batteries and runtime
Battery type
Maintenance-free sealed lead-acid battery with suspended electrolyte; leak proof
Replacement battery
RBC48 RBC6 RBC7 RBC55
Runtime estimates
200 W
:22 :45 1:24 2:17 2:29
500 W
:05 :10 :23 :51 :55
700 W
:06 :12 :34 :37
1,000 W
:07 :21 :23
1,400 W
:13 :14
1,600 W
:10 :12
Full load
:05 :06 :07 :07 :06
Communication and management
Interface ports
Serial (RJ45), USB, and SmartSlot
Control panel and audible alarms
Alpha-numeric LCD display with LED status indicators; alarm on battery,
distinctive low battery alarm and configurable delays
Emergency power off (EPO)
Optional Yes
Surge protection and filtering
Surge energy rating
459 J 480 J
Filtering meets
Full-time multi-pole noise filtering: 0.3% IEEE
surge let-through, zero clamping response time,
meets UL 1449
Physical
Maximum height (inches)
6.2 8.5 8.5 17.0 17.0
Maximum width (inches)
5.4 6.7 6.7 7.7 7.7
Maximum depth (inches)
14.1 17. 3 17. 3 21.5 21.5
Net weight (pounds)
29 42 53 112 116
Conformance
Regulatory
UL 1778, CSA
Warranty and equipment protection policy
3-year electronics, 2-years battery, and $150,000 lifetime EPP
=
Page view 4
1 2 3 4 5 6 7 8

Comments to this Manuals