3 Symmetra® PX 10-80 kW 208 V Site Preparation Guide - 990-1425A
Operating Environment
Space Considerations
Install the UPS in an Indoor, Controlled Environment
Temperature
Range: 32°-104°F
KeepVentilated
Front-to-Rear
Airflow
Relative
Humidity: <95%
Non-condensing
No Conductive
Dust or
Corrosive Fumes
Max.
Elevation:
10,000 ft.
Full Load Heat Loss at Nominal Mains: 23,743 BTU/hr (6,957 Watts)
CAUTION!
If the UPS exceeds doorway height, remove from pallet and wheel through door (see
Overview of System Components section for UPS height excluding pallet).
Front-to-rear
airflow
Floor-to-ceiling
ventilation:
> 91 in/2300 mm
24 in/610 mm
36 in/915 mm
36 in/915 mm
Minimum front clearance
Minimum rear clearance
Stabilizing feet
UPS
47 in/1200 mm
91 in/ 2300 mm
36 in/915 mm
CAUTION!
The UPS and the XR Battery Enclosure are heavy. Ensure that the floor and sub-floor
can support the total weight of the configuration when concentrated on the stabilizing
feet.