String Polarity Mismatch. The second battery string’s polarity is reversed
from the polarity of the first battery string. The Battery Management System
will not detect the second string if its polarity is reversed.
Battery String A Missing. Minor Alarm. At start-up, the Battery
Management System twice attempts to detect the polarity of Battery String
A. If both attempts fail, the Battery Management System generates a
Battery String A missing fault.
Blown Fuse or Open Circuit on Battery String Connector. Minor
Alarm. The BMS detects an individual battery voltage of less than 3 VDC.
Possible Causes Corrective Action
Second battery strings
polarity does not match
the first string’s polarity
• Reverse the order of the battery leads connected to one
of the battery strings.
Possible Causes Corrective Action
Single battery string is
connected to the String B
input
• Connect the battery string to the String A connector. If
you are using only one battery string, it must be
connected to the String A input.
Blown battery lead fuse on
String A, Battery #1
• Replace the blown battery lead fuse.
Possible Cause Corrective Action
Blown battery lead fuse • Replace the blown battery lead fuse.
Open circuit in the battery
wiring harness
• Check the battery wiring harness connections.