USERS GUIDE
battery management system
4
Set the DIP switches
After disconnecting the input power, reset the DIP switches to configure the
change in your system.
The DIP Switches must be set to one of the following valid
configurations. If the DIP switches are set incorrectly, your
Battery Management System may not operate properly.
Condition Switch Number
87654321
Gel Batteries* Off
AGM Batteries On
Four Batteries per string * Off Off
Three Batteries per string Off On
Two Batteries per string On Off
Ambient Temp Compensation* Off
Battery Temp Compensation On
25 Amp Hour Batteries * Off Off Off Off
30 Amp Hour Batteries Off Off Off On
35 Amp Hour Batteries Off Off On Off
40 Amp Hour Batteries Off Off On On
45 Amp Hour Batteries Off On Off Off
50 Amp Hour Batteries Off On Off On
60 Amp Hour Batteries Off On On Off
70 Amp Hour Batteries Off On On On
*Default Setting