USERS GUIDE
battery management system
6
Install a current sensor
If you add a second battery string to a system that had only one string, you
need to install a second current sensor. The system needs one sensor per
string to measure the current throughout the string.
1. Set the DIP switches on the new current sensor to identify its location
correctly.
2. Plug the ambient temperature sensor into the unused port on the
current sensor to be located at the warmest area of the enclosure.
Connect the two current sensors to each other with the supplied cable.
3. Use the remaining cable to connect the sensor string to the sensor port
at the back of the Battery Management System. Unless at least one
current sensor is connected to the sensor port, neither current sensor
will be able to report information. If a current or temperature sensor is
not functioning, always check this connection first.
4. Calibrate the new current sensor.
5. Install the current sensor in the new string, ensuring that the current
sensor is oriented correctly with a load carrying conductor passing
through it.
S
ee a
l
so
See the Installation and Quick-Start Manual for detailed
instructions on calibrating the current sensors.
S
ee a
l
so
For detailed instructions on how to install temperature and
current sensors and to set the DIP switches correctly, see the
Installation and Quick-Start Manual.