FacilityPlanning
ACInputSpecications
Note:Allcurrentvaluesarebasedona40kWmaximumconguration.
40kWSystem
Connectiontype
3PH+N+G
Inputvoltage(V)3–Phase208V(166V-240V)
Inputfrequency(Hz)
40–70
THDI
<6%atfullload
Nominalinputcurrent(A)
123
Maximuminputcurrent–continuous,atminimum
mainsvoltage(A)
154
Inputcurrentprotection(externaltoUPS,notsupplied)
1
175
MaximumShortCircuitWithstand(kA)
30
1
Input:175Amp.3-PoleACcircuitbreakerwith30kAIC.
Note:IfyourinstallationdoesnotincludeanIsolationTransformerandaMBP(optional
equipment),usea175AmpClass“J”currentlimitingfuseoneachinputphase.
ACBypassInputSpecications
40kWSystem
Connectiontype
3PH+N+G
Inputfrequency(Hz)
40–70
Nominalinputcurrent(A)
111
ACOutputSpecications
Outputvoltage
208V
Connectiontype
3PH+N+G
Overloadcapacity150%for30seconds(normaloperation)
150%for30seconds(batteryoperation)
125%continuous(bypassoperation)
1000%for500ms(bypassoperation)
Nominaloutputcurrent(A)
111
Maximumoutputcurrent(inbypassonlyat125%
overload,perphase)(A)
139
Neutraloutputcurrentwith100%switchmodeload(A)
1
192
Outputcurrentprotection–externaltoUPS,not
supplied(A)
2
150
990–4641–001
SymmetraPX10–40kW208VTechnicalSpecications