Outputfrequency(online,inbypass)
3
Synchronizedtoinputovertherange57Hz63Hz
Outputfrequency(onbattery)(Hz)50/60
Slewrate(Hz/s)Programmableto0.25,0.5,1,2,4,and6
THDU
<2%linear
<5%non-linear
1
Neutraloutputwires:ratefor173%ofoutputphasecurrentiffeedingallSwitchModePowerSupplyloads
withoutpowerfactorcorrection.
2
Output:150Amp3-poleACcircuitbreakerwith30kAIC.
3
Thefollowingrangescanbeselected:40-60Hz,47-53Hz,49.9-50.1Hz,50-70Hz,57-63Hz,and59.9–60.1Hz
BatterySpecications
Type
VRLA
Nominalvoltage(VDC)+/-192(96cellsat2V)
Floatvoltage(VDC)+/-219(96cellsat2.28V)
1
Endofdischargevoltageatfullload(VDC)+/-158(96cellsat1.65V)
Maximumchargingpower4kW(5kWifredundantPowerModuleispresent).It
maydroptolowervalesatlowACMains.
Typicalrechargetime(to80%ofcapacity)3.5hours
1
Floatvoltageistemperaturecompensated.Itisdecreased320mVperºCfortemperatureshigherthan20ºC
RecommendedCableSizes
Caution:Allwiringmustcomplywithallnationaland/orlocalelectricalcode.
Note:Therecommendedcablesizesarebasedinanenvironmentwithanambient
temperatureof40°C(104°F)
Note:Neutraloutputwires:ratefor173%ofoutputphasecurrentiffeedingallSwitch
ModePowerSupplyloadswithoutpowerfactorcorrection.
Note:Groundwires:sizedinaccordancewithNECArticle250-122andTable250-122.
Note:Maximumcablesizes:250kcmil.
Input
2/0AWG90°C(194°F)ratedcopperwire.
Output
1/0AWG90°C(194°F)ratedcopperwire