49User Guide InfraStruxure 150kVA Power Distribution Unit
brkrAdd
Access: Administrator, Device
Description. Add a breaker at the panel position selected by the brkrTarget and brkrPanel commands.
The required inputs are the number of poles, the CT rating and breaker rating.
Parameters: <# poles> <CT> <Rating>
#poles = number of poles the breaker protects (must be 1,2,3)
CT = rating of the current transformer monitoring the positions (must be 50 | 100)
Rating = rating of the breaker being monitored (must be <= 100)
Example.
apc> brkrPanel 2
1. 2.2,p2 2,,,21A,50A,Normal,0.0kW,0.0kWh,03/02/2012
2. 2.2,L1,0.0A,0.0%,2.4,L2,0.0A,0.0%
3. 2.10,Brkr 10 + 12,pb2 10-12,,20A,50A,Normal,2.2kW,1489.5kWh,03/02/2012
4. 2.10,L2,9.4A,47.0%,2.12,L3,9.3A,46.5%
5. 2.18,Unknown,Unknown,Unknown,45A,50A,Normal,0.0kW,0.0kWh,05/04/2012
6. 2.18,L3,0.0A,0.0%
7. 2.20,Unknown,Unknown,Unknown,35A,50A,Normal,0.0kW,0.0kWh,05/04/2012
8. 2.20,L1,0.0A,0.0%,2.22,L2,0.0A,0.0%,2.24,L3,0.0A,0.0%
9. 2.42,42,,,42A,50A,Normal,0.5kW,1044.1kWh,03/02/2012
10. 2.42,L3,4.8A,11.4%
apc> brkrTarget 14
Breaker position not currently in use.
apc> brkradd 3 50 30
1. 2.14,Unknown,Unknown,Unknown,30A,50A,Normal,0.0kW,0.0kWh,05/04/2012
2. 2.14,L1,0.0A,0.0%,2.16,L2,0.0A,0.0%,2.18,L3,0.0A,0.0%
Error Messages: E102