InRow RD Technical Data Manual46
Guide Specifications
PART 1 — GENERAL
1.01 SUMMARY
A. The environmental control system shall be designed specifically for precision temperature control
applications. It will automatically monitor and control cooling and filtering functions for the
conditioned space. The system shall be built to the highest quality engineering and manufacturing
standards, and shall be floor mounted and configured for horizontal airflow, with draw-through air
pattern, to provide uniform air distribution over the entire face of the coil.
1.02 DESIGN REQUIREMENTS
A. The system shall be as described in the following specification as manufactured by APC.
1. Model: ____________________________.
2. Total net cooling capacity: _______________ kW (MBH).
3. Sensible net cooling capacity: ____________ kW (MBH).
4. Return air dry bulb temperature: _______________ ºC (ºF) DB.
5. Return air wet bulb temperature: _______________ ºC (ºF) WB.
6. Humidity: __________________________% RH.
7. Air volume: _______________________ L/s (CFM).
8. Electrical supply: ____________ V, _________ Hz.
1.03 SUBMITTALS
A. Submittals shall be provided with the proposal and shall include: capacity data, electrical data,
physical data, electrical connection drawing, and piping connection drawing.
1.04 QUALITY ASSURANCE
A. The system shall be completely factory-tested prior to shipment. Testing shall include, but not be
limited to: complete pressure and leak testing to ensure system integrity, dielectric withstand test,
and controls calibration and settings. Each system shall ship with a completed test report to verify
completion of factory testing procedure. The system shall be NRTL listed, MCA, and the electrical
system shall be UL Listed to UL 1995 and CSA 22.2 No. 236.
1.05 WARRANTY
A. System parts shall be warranted for a period of 18 months from date of shipment and 12 months