5InRow RD Technical Data Manual
Optional Features
Cable Water Detector
A leak detection cable is placed on
the floor or subfloor around all possi-
ble leak sources. If water or other
conductive liquids contact the cable
anywhere along its length, the micro-
processor controller announces the
leak visually, audibly, and across the
network. The 6.1-m (20-ft) cable
may be cascaded to make custom
lengths up to 24.4 m (80 ft).
Network Cable
Various lengths of network cable are
available to ship with your cooling
system. The network cable is used to
interconnect multiple cooling units in
a redundant group, as well as to con-
nect the Network Management Card
to your LAN.
Filters
Electrical equipment requires clean,
particle free air, thus making air fil-
tration extremely important. As an
optional feature, higher efficiency fil-
ters can be purchased for the InRow
RD units. The ACRD100 and
ACRD200 series units optionally uti-
lize an 50.8mm (2in) pleated, deep
loading, 30% ASHRAE 52.1 filter
(MERV 8 per ASHRAE 52.2). The
ACRD500 series units optionally uti-
lize 102mm (4in) pleated, deep
loading, 85% ASHRAE 52.1 filter
(MERV13 per ASHRAE 52.2).
Power Trough
Overhead power distribution between
adjacent NetShelter racks allows for
removal of the InRow RD without
disrupting overhead power cabling.
Data Partition
Overhead cable distribution between
adjacent NetShelter racks allows for
removal of the InRow RD without
disrupting overhead cabling.
Height Adapters
To match the height of the InRow RD
to various rack heights, height adapt-
ers are available for NetShelter 42-U
VX and 48-U SX racks.