Redundant Switch - Applications Guide March 22, 1999
19
Application #6. Smart-UPS Bypass
Configuration
Power to
Redundant Switch
A
B
Redundant
Switch
Power
to Load
AC
communications
Surge Arrest
Rackmount
EPO
Emergency
Power Off
R
T
N
I
N
+
2
4
Function
StatusSelect
StatusSelect
To UPS BAC SourceTo UPS A
B
A
Level
Source selectedBright
Source OK, but not selectedDim
Source not OKOff
To Server
Redundant Switch
Goals and objectives
Redundant Switch can be used with a single Smart-UPS unit to provide bypass functionality. Redundant
Switch allows the user to service or upgrade the Smart-UPS in the application without interrupting power
to the load (no need for scheduling downtime).
The Surge Arrest Rackmount Unit provides surge filtering to the loads when you select power from source
B at the Redundant Switch front panel. A surge could effect load operation and functionality when
Redundant Switch is in bypass mode and an APC Surge product is not in the bypass path. For this reason,
APC’s Equipment Protection Policy does not apply to a bypass configuration without an APC Surge
product in the bypass path.
Redundant Switch Function Settings
Use the factory preset settings (defaults).
Installation
Smart-UPS unit: Follow the instructions and procedure given in the Smart-UPS User’s Manual or Smart-
UPS Rack Mount Supplement.
Redundant Switch: Redundant Switch mounts in the front or the rear of a standard 19” cabinet, occupying
1U of rack space.
Follow the Redundant Switch User’s Manual Initial Start-Up instructions.
Power the critical loads that you will need to keep up during Smart-UPS maintenance or a Smart-UPS
upgrade through Redundant Switch. Power non - critical loads directly from the Smart-UPS unit.
Operation
The Smart-UPS unit communicates directly with the server, The Smart-UPS units provides power to the
server through Redundant Switch, Source A. Redundant Switch has Source A set as the preferred source.
To bypass the Smart-UPS unit, switch the preferred source to source B (at the Redundant Switch front
panel). When the service or upgrade tasks complete, switch the preferred source back to source A (at the
Redundant Switch front panel). Refer to the Redundant Switch User’s Manual.