EPO Switch Wiring
The UPS must be connected to either a dry contact or a 24 Vdc
Emergency Power Off (EPO) switch.
The EPO circuit is considered Class 2 and SELV (Safety Extra Low
Voltage). A SELV circuit is isolated from primary circuitry through an
isolating transformer and designed so that under normal conditions, the
voltage is limited to 42.4 Vac peak or 60 Vdc. SELV and Class 2 circuits
must be isolated from all primary circuitry. Do not connect any circuit to
the EPO terminal block unless it can be confirmed that the circuit is
SELV or Class 2.
For installations in US.
CL2Class 2 cable for general purpose use.
CL2PPlenum cable for use in a vertical shaft or from floor to
floor.
CL2R Racer cable for use in dwellings and raceways.
CL2XLimited use cable for dwellings and raceways.
For installations in Canada.
CL2RCertified, type ELC (Extra-Low-Voltage Control Cable).
CL2XCertified, type ELC (Extra-Low-Voltage Control Cable).
Communication Cables
Side panel removal
Warning: Ensure Total Power Off before removing the
side panel (see Total Power Off procedure in the Safety
Sheet).
Note: Use 20-foot standard Cat 5 data cable (supplied). If the
cable length is inadequate, a longer Cat 5 cable, or couplers,
can be used (not supplied).
Note: If bottom routing is required, follow steps 1 to 5 below
to gain access to the communication cables. If not, proceed to
Connecting communication cables.
Unlock the right-side panel using key.
Depress the latches.
Pull out the panel.
Lift the panel at an angle away from the enclosure.
Route the communication cables through the front holes of the
enclosures. Exit the enclosures from the bottom or top as required.
Note: If your UPS has been installed between devices and
side panels cannot be removed, the Bypass Static Switch
Module can be removed to gain access.
How to connect communication cables
Connect the network communication cable.
Connect the XR communication cable.
See Also: Refer to the guide supplied with the battery
enclosure for further details on how to connect
communication cables between the UPS and the XR Battery
Enclosures.
Installation and wiring of optional
APC Maintenance Bypass Panel
Wiring overview
J6
Input/Output Wiring of Ancillary Equipment
J6
1
1 Internal Power
+24V Supply
2
4
3
2/3 Relay Coil 1
4 Ground
EPO Control for PSX PDU
Emergency
Power OFF
Switch
Keep EPO
wire routing
isolated and
use separate
EPO conduit
AC
Output
AC
Input
DC Input
(Optional XR)
1/2 Battery Breaker present
4 Ground
N/O EPO Control N/C EPO Control
3/2 Relay Coil 1
1 Internal Power
+24V Supply
8 Ground
7/6 Relay Coil 2
5 Internal Power
+24V Supply
3/4 Ext. battery fuse/Battery Breaker 1
(N/O position)
5/6 Ext. battery fuse/Battery Breaker 2
(N/O position)
7/8 Temp. sensor, ext. battery
9/10 Temp. sensor, ext. battery present
11/12 Iso. trafo temp. switch (N/C position)
13/14 Iso. trafo temp. switch present
Emergency shut-down with internal supply
XR Communications
Port 1
Port 2
Display / Computer Interface
Display
Remote
Power View
Computer
Interface
Reset
Link-RX/TX
S
tatus
10Base-T
AP9606 PowerNet Network Adapter
System Power Supply
Battery Monitor
MBP
(optional
equipment)
Output
Power
Input
Power
Battery Enclosure
(Optional, 4 Max.)
EPO
AC Power
DC Power
Interface wiring