20 UPS Network Management Card 2 User’s Guide
The ups command options for MGE Galaxy-specific UPS devices:
These commands are only available on the MGE Galaxy 300 and MGE Galaxy 7000 UPS. Some
options may only be available based on the individual UPS model.
Example 1: To initiate a runtime calibration, type:
ups -r start
Example 2: To immediately turn off outlet group 2 at a Smart-UPS XLM, type:
ups -o2 off
upsfwupdate
This command might not be available for all UPS devices.
Access. Super User, Administrator, Device User.
Description: Initiate an update of the UPS firmware. The firmware update file must have been previously sent
using FTP to the NMC and stored in the /upsfw/ directory.
Option Argument Description
-input
<phase#> | all
Display the input measurements for the chosen phase of the UPS.
Typing “all” displays the information for all phases of the UPS.
voltage | current |
frequency | all
Specify the input measurement for the ups command.
Example: ups -input 2 frequency
Displays the frequency for phase 2 of the UPS.
-bypass
<phase#> | all
Display the input measurements for the chosen phase of the bypass
main. Typing “all” displays all phases of the bypass main.
voltage | current |
frequency | all
Specify the input measurement for the ups command.
Example: ups -bypass 2 current
Displays the current for phase 2 of the bypass main.
-output
<phase#> | all
Display the output measurements for the chosen phase of the UPS.
Typing “all” displays the information for all phases of the UPS.
voltage | current | load |
power | percload | pf |
frequency | all
Specify the output measurement for the ups command.
Example: ups -output 2 percload
Displays the percentage of load for phase 2 of the UPS.
-batt Display the battery status of the UPS
-about Displays information about the UPS.
-al c | w
Display all existing alarms. Specifying “c” or “w” limits the display to
either Critical (c) or Warning (w) alarms.
Option Argument Description
-apply Start the firmware update.
-status Check the status of a firmware update that is already initiated.
-lastresult View the result of the last attempted firmware update.