Section 6: SPDU Guide Specifications
64 SPDU Technical Handbook
D. Full-frame Floor Stand
1. A full-frame floor stand must be available for enclosure leveling, and as a means of
providing bottom cable access independent of a raised floor application.
2. The floor stand must be constructed of welded steel, and be offered in heights of up to 32
inches with an adjustable range of +/- 3 inches.
E. Input Surge Arrestor
1. A multi-stage suppression circuit device must be available as a means of arresting input
surge. This device would utilize fast-acting 40 mm Metal Oxide Varistors (MOVs) and be
connected in a high-energy, parallel design for Category A, B, and C3 applications. Each
mode of protection would be individually fused, and contain a thermal cutout to ensure
safe operation during severe over-voltages and high fault-current conditions. The device
must have an interrupting rating of 100,000 RMS symmetrical amperes, and be capable of
withstanding 5,000 Category C3 impulses with less than 10% drift.
2. The suppression circuit device must also have an AC tracking filter to provide wave
shapes smoothing. It must further provide a high level of EMI/RFI noise attenuation, as
well as electrical noise attenuation of up to -50 db from 100 kHz to 100 MHz. The device
must be installed with a minimum conductor length in order to achieve maximum
performance.
3. For Basic and Advanced-level monitoring systems, this device should offer a remote
monitor that is mounted on the front panel of the SPDU as an added option. For the
Premium-level monitoring system, this device should offer an alarm contact that connects
with the monitor to annunciate suppression device failures as an added option.
PART 3 — EXECUTION
3.1 SERVICE
A. Factory start-up and user training, preventive maintenance service, and full service for the
above-specified system must be included upon request. The manufacturer must also employ an
international service organization that consists of factory-trained field service personnel who
are dedicated to the start-up, maintenance, and repair of all provided power equipment.
B. The manufacturer must further maintain a full-time (24 hours per day, 365 days per year) call
center to provide readily available technical support to end users and to facilitate emergency
service dispatching.
End of Section 16460