Smart-UPS® VT 10-40 kVA, 200/208 V, 208/220 V, 380/400/415 V24
Recommended power connection with 3-phase 3-wire (delta wiring) with one phase
grounded.
Recommended power connection with 3-phase 4-wire with neutral grounded.
Note 1: If the input utility source has delta wiring with one phase grounded, do not connect one phase of
the output delta wiring to the ground. This is to prevent any malfunction of the UPS system and the load
equipment.
Note 2: If the two input utility sources have delta wiring with one phase grounded, the two utility input
sources must have the same frequency and phase which is supplied by the same power source. This is to
prevent any malfunction of the UPS system and the load equipment.
POWER SOURCE UPS POWER DISTRIBUTION UNIT
POWER SOURCE UPS POWER DISTRIBUTION UNIT
POWER SOURCE UPS LOAD
Note 1
Note 2
Page view 27