InRow RD Operation and Maintenance20
Contacts
View the state of Input and output contacts
Path: Main > Configure Unit > Discrete I/O
Each cooling unit supports a user-defined input contact and a user-defined output contact. Each contact
monitors a sensor and responds to changes in the state of the sensor (open or closed).
Input State. Indicates the actual state of the input contact (open or closed). A cooling unit is On when
the state is normal and in Standby when the state is not normal.
Output State. Indicates the actual state of the output contact (open or closed). An alarm will cause the
output contact to change from the normal state.
Edit the normal state of input and output contacts
Path: Main > Configure Unit > Discrete I/O > Normal State
You can set input contacts to cause alarm conditions based on a user-defined normal state. Output
contacts can map internal alarms and events to outside devices.
Input Norm. Set the normal state of the contact (open or closed). The cooling unit changes its operating
mode to Standby when the actual state differs from the normal state.
Output Norm. Set the normal state of the contact (open or closed). If the state of an alarm or event
mapped to this contact changes from the normal state, the contact also changes state.
Outpt Src. Define the type of output source (alarm), either Any Alrm or Critical, that causes the output
to change from its normal state.
Cooling Group Configuration
The cooling group configuration settings determine which components are available and how the cooling
group should operate.
Caution: This procedure is to be performed by APC authorized personnel only. The settings
in the Cooling Group Configuration menu are defined by APC authorized personnel when
the cooling group is commissioned.
Configure the cooling group
Path: Main > Configure Group
The Configure Group menu contains settings that identify the number of cooling units installed in this
cooling group and the physical arrangement of those cooling units.
Num Units. Enter the number of cooling units in this cooling group. Up to 12 cooling units can be
joined together to work as a single cooling group.