Guide Specifications
20 APC InRow SC Technical Data Manual
Ceiling tile adapter shall be suitable for either 24in x 24in or 600mm x 600mm suspended
ceiling grids and constructed of powder coated metal.
M. CABLE WATER DETECTORS (OPTIONAL)
1. A leak detection sensing cable shall be shipped loose with the unit. If water or other
conductive liquids contact the cable anywhere along its length, the main controller
visually and audibly annunciates an alarm.
2. The detector shall be provided with a 20ft (6.1m) of cable. Additional cable may be
cascaded up to 80ft (24.4m) total length. A total of four water detectors are available per
unit.
N. CABLE SUPPORT BRIDGE TROUGH (OPTIONAL)
Overhead cable distribution bridge shall connect to adjacent racks and allow for removal
of the unit without disrupting the cable connections. The trough shall be made of 16 gauge
metal with powder coat finish. Trough shall be capable of carrying no less than 80 CAT5
cables.